Pump Churn Pressure

• Definition: Pump churn pressure is the pressure developed by a fire pump when it operates at zero flow, meaning that the pump is running with its discharge outlet closed and no water is being delivered to the fire water network. It is also known as shut-off pressure. For centrifugal fire pumps, churn pressure is an important characteristic of the pump performance curve and is generally higher than the rated discharge pressure.

• Example: Consider a centrifugal fire pump having a rated capacity of 1000 GPM (approximately 227 m³/hr) at a rated pressure of 8 bar. When the pump operates with zero discharge flow, its pressure may rise to approximately 10 bar. This no-flow pressure is known as the churn pressure. The actual value should be verified against the manufacturer's certified pump performance curve and applicable design requirements.

• Why it matters: Churn pressure is important for understanding the maximum pressure that a centrifugal fire pump can develop under no-flow conditions. It helps engineers assess the pressure rating of fire water pipelines, valves, fittings and connected equipment. Excessive churn pressure can expose system components to pressures beyond their design limits. During routine testing, the churn condition also helps verify the pump's no-flow performance and identify abnormal changes from its baseline performance.

• Related terms: Fire Pump, Rated Pump Capacity, Rated Pump Pressure, Fire Pump Performance Curve, Pump Shut-off Head, Fire Pump Performance Test, Jockey Pump.